0000006520 00000 n 0000005933 00000 n 0000003034 00000 n 0000027455 00000 n hot-spot calculation of the oil temperature. relay setting calculation scribd. MiCOM P546 Calculations. transformers on the high-voltage side and the second group including T4, T5 and T6 is connected to the corresponding current tran sformers on the low-voltage side of the power transformer. 0000005904 00000 n calculations of protective relay settings transformer. 0000085543 00000 n In some instances where there is not a high voltage panel, there is a fused disconnect instead. Again assume type A: Ires at PT2 = 2*IFLres = (0.655+0.555)*2 = 2.42 A. 0000003308 00000 n 0000003831 00000 n For this example, a Minimum Pickup setting of 0.1 pu is equal to 0.1×1000 A = 100 A differential current. Say current setting of the relay is 150 % therefore pick up current of the relay is 1 × 150% = 1.5 A. Step-3 Now we have to calculate PSM for the specified faulty current level. Setting procedures are only discussed in a general nature in the material to follow. For that, we have to first divide primary faulty current by CT ratio to get relay faulty current. 0000005341 00000 n 0000006012 00000 n A single line diagram of the power system. Thus Differential Protection will operate if the Slope is greater than some fixed value which is set in the Differential Protection Relay. Transformer impedance=11 % at 20 MVA base. 0000002073 00000 n INTRODUCTION To prevent faults and to minimize the damage in case ot a fault, transformers are equipped with both protective relays … MiCOM P546 Calculations. Relay setting Calculation. Thermal Over Load Relay vs CT operated thermal overload Relay: Thermal over relay: Thermal overload relay is simple over current protection, it does not protect from single phasing or phase failure, short circuit, and earth fault.The operating principle of the relay is, when current flow through a conductor increases then I^2 X R loss also increases (Heat loss or ohmic loss). Relay pick up current Primary side = 1.05 * 600 = 630A. Transformer Diff. Cable impedance=.015*4=0.06 ohm. 0000001938 00000 n For most cases a turning point of 2 (corresponding to twice rated load) suffices. The considerations for a transformer protection vary with the application and importance of the power transformer. 0000004207 00000 n Transformer Differential Protection Setting Calculation . ABB RED670 Fault Locator Calculations. Mohammed Tawfeeq 011 Power system protection Dr.Mohammed Tawfeeq Overcurrent Protective Relays Overcurrent relays Overcurrent relaying is the simplest and cheapest type of protection used for protection of lines, transformers… 0 From current setting we calculate the trick current of the relay. 0000010348 00000 n 0000004553 00000 n Base MVA=100 Fault MVA=1200 Source impedance=0.083 Cable impedance=.015*4=0.06 ohm Transformer impedance=11 % at 20 MVA base =0.11*100/20=0.55 ohm Total fault impedance at 6 kV Bus=0.083+.06+.55=0.693 ohm. 0000003012 00000 n IDMT Curves; Transformer Differential. 0000008314 00000 n 0000002456 00000 n Our digital library saves in compound countries, allowing you to acquire the most less latency times … 0000009156 00000 n 400/220KV TRANSFORMER DIFFERENTIAL PROTECTION SETTING 1. 0000085343 00000 n MiCOM P643 Calculations. 0000009941 00000 n There setting methods are same but the only difference is that pick up of 51 is … For that, we have to first divide primary faulty current by CT ratio to get relay faulty current. The electrical quantity may be voltage or current. 0000005614 00000 n This setting should be larger then the transformer magnetizing cur-rent and steady state CT errors during no load conditions. 0000007075 00000 n The following protection functions are used in this relay. Line Differential. RET615 is a dedicated transformer protection and control relay for protection, control, measurement and supervision of power transformers, unit and step-up transformers, including power generator-transformer blocks, in utility and industrial power distribution systems. We have calculated New PSM =0.7875. 0000004620 00000 n transformer protection application guide ieee. setting is 100/5 A and the fault current is Scribd è il più grande sito di social reading e publishing al mondo. Differential Protection Setting Calculations ƒ87H Pickup - Typically set at 8 to 12 pu rated current - This value should be set to above the maximum possible inrush current. Transformer Differential Protection Scheme works by using two separate quantities calculated from the primary current (IW1C) and secondary current (IW2C). Transformer Protection Application Guide This guide focuses primarily on application of protective relays for the protection of power transformers, with an emphasis on the most prevalent protection schemes and transformers. startxref PART-1CT RATIO SELECTION FOR REF RELAY SETTINGIn this video we have explained calculation of CT ratio for restricted earth fault relay setting calculation. 0000002163 00000 n guidelines for relay settings at traction. Overcurrent protection for a transformer on the primary side is typically a circuit breaker. 0000004303 00000 n 180 0 obj << /Linearized 1 /O 183 /H [ 2054 980 ] /L 367823 /E 86102 /N 22 /T 364104 >> endobj xref 180 71 0000000016 00000 n 0000003417 00000 n Protection selectivity is partly considered in this report and could be also re-evaluated. overcurrent protection is available for each winding or measurement location of a transformer. 2.1 Differential Relay Settings Calculations MiCOM P63X Relay Type: MICOM P63X Required Data Ratings of the Power and Current Transformers MVA Voltage Ratio Rated Voltage in kV (HV Side) Rated Voltage in kV (LV Side) Vector Group CT Ratio (HV Side) CT HV Side Vector Group CT Ratio (LV Side) CT LV Side Vector Group … relay settings, over current relay settings, idmt relay setting, earth fault relay setting, instantaneous relay setting, how to set relays, relay setting calculation, relay characteristics, calculation to set relays, IDMT relay setting calculation 0000013858 00000 n Transformer Protection Application Guide This guide focuses primarily on application of protective relays for the protection of power transformers, with an emphasis on the most prevalent protection schemes and transformers. transformer protection relay setting calculation guide pdf is affable in our digital library an online entrance to it is set as public thus you can download it instantly. 0000003519 00000 n 0000006901 00000 n (1) Low over Current Setting: (I>) Over Load Current (In) = Feeder Load Current X Relay setting = 384 X 125% =480 Amp Required Over Load Relay Plug Setting= Over Load Current (In) / CT Primary Current Required Over Load Relay Plug Setting = 480 / 600 = 0.8 Pick up Setting of Over Current Relay … 0000005519 00000 n It is normal for a modern relay to provide all of the required protection functions in a single package, in contrast to electromechanical types that would require several relays complete with interconnections and higher overall CT burdens. 0000007302 00000 n Other similar relays use similar concepts through the actual terminology could be different. Case-2 for New CT: New CT Ratio- 800/5A. 0000004274 00000 n ABB RET670 Calculations. 3.2. Fault MVA= 100 MVA/0.693=145 MVA=150 MVA (approx) 3 phase fault current at 6 kV bus=150/1.732*6 =14 KA. Relay setting Calculation. ANSI C57 Transformer Thru Fault Curves, Impact of Transformer Winding Configuration, Overview of Differential Protection, Inrush and Harmonic Restraint, Hands On Differential Relay Setting Calculation Problems and Calculation Worksheets. Should a fault occur inside the zone of relay protection (that is between the CT’s), the differential relay would receive current in the operating coil. Call us 800.874.8883 (U.S.) or email. ASS Relays Power transformer protection AGO3-5005 E Page 3 1. ABB RET670 Calculations. 0000066338 00000 n 0000002298 00000 n 0000003278 00000 n This technical report refers to the electrical protection of all 132kV switchgear. 0000001980 00000 n 0000004649 00000 n Relay Pickup current (Primary) = Plug Position (PSM) * Rated CT Primary current. 0000006393 00000 n 0000006647 00000 n Base MVA=100. Our digital library saves in compound countries, allowing you to acquire the most less latency times … Say current setting of the relay is 150 % therefore pick up current of the relay is 1 × 150% = 1.5 A. Step-3 Now we have to calculate PSM for the specified faulty current level. Let for differential Protection to operate, Id should be greater than the x% of Ib. The following data are required for finding out the setting of the relay. 0000004879 00000 n The example differential protection relay shown in the below figure is a transformer differential relay. Set- tings calculations for many of these relays are straightforward and are outlined in the relay’s applications manual. It is normal for a modern relay to provide all of the required protection functions in a single package, in contrast to electromechanical types that would require several relays complete with interconnections and higher overall CT burdens. - Relay oscillograph analysis software can be used determine the inrush current level and fine tune the setting. It is important to note that the overcurrent device on the primary side must be sized based on the transformer KVA rating and not sized based on the secondary load to the transformer . Names of parameters in this calculation may differ from those in the appropriate device. H�b```f`�`c`��� � ea��`Hbfa0Hpa�ppP`�����w������9>�����:��`�c��oG�cw^�x�d��~��j�p�%Sv�. relay 51T = High Side Phase OC relay 51 = Low Side Phase OC relay 51G = Low Side Ground OC relay 51GB1,2 = Ground Backup OC relay 51G 51GB1 51 51GB2 51TG = High Side Ground OC relay 87K-S 87K-P 87K-S = Sec. But mostly voltage based relays are not preferred. Source impedance=0.083. In order to make these calculations, knowledge of peak- load current, minimum and maximum fault currents, and the CT and VT ratings is required. website. trailer Principles are emphasized. Tap Compensation Equation The transformer MVA rating is 33MVA while the voltage rating is 23kV. protection functions used for large utility electric power transformers, and how the protection setting calculations and actual relay settings are affected when protecting three single-phase transformers. Differential Relays 2. [Since the bias current is less than 1.5 A the slope will be within 30%] Therefore the operating current of the relay will be = Is + (m1+m2)* I bias = 0.1 + (0.4 +0.8) * 0.754 = 1.01 A The operating value is larger than the differential value hence the system is Stable for the MAX tap condition. 27 differential relay electrical4u com. overcurrent protection is available for each winding or measurement location of a transformer. 312 16 0000004078 00000 n My Protection Guide. The considerations for a transformer protection vary with the application and importance of the power transformer. 0000002054 00000 n Id =I1s - I2s In principle, this basic approach of a di fferential protection scheme is implemented using an overcurrent relay placed in the di fferential current path formed … 0000085211 00000 n endstream endobj 313 0 obj <. Total fault impedance at 6 kV Bus=0.083+.06+.55=0.693 ohm. 0000001771 00000 n calculation: IDMT Characteristics . 0000085409 00000 n 0000010122 00000 n 1. 87B = Bus Differential relay 87K-P = Pri. Fault MVA=1200. Selection of the protection … 0000000633 00000 n DIFFERENTIAL PROTECTION SETTING Relay: Micom P633 Recommended Differential Setting = 0.20 Amp Transformer rating : 315 MVA, 400/220 KV, Impedance12.5 % Tap +10 % ( 440 KV - 360 KV ) HV Side CTR - 1000:1 LV Side CTR - 800:1 At normal condition current in LV bias … Percentage differential relay or Biased Differential Protection: Generally differential protection relay means the relay operates when the phasor difference between the two or more electrical quantities exceed the pre-set value. Principles are emphasized. Protection relay codes 24 8. Setting example for transformer protection An example for setting the REF542 plus for transformer protection will be described in the following section. SEL787 and SEL 387/587 Transformer differential relay is used for this discussion. xref calculation: IDMT Characteristics . Transformer Differential Protection Scheme works by using two separate quantities calculated from the primary current (IW1C) and secondary current (IW2C). Substations We use to prefer current based differential protection, but […] They generally have current setting multipliers ranging from 50 to 200% in steps of 25% which is refered to as plug setting [PS] for each relay is determined by the fault current [7]. A̵��Nl:,#�pk�^�i"��8�������'�ͻ�I���ps���E:��M�P��+[xp{�+���v�@9�թ�z��kn�z�Ř�]ҽS5� u�_��Ņ�cBJ�I�n��}���"�ޠ��r &iG]R��p����˙�B��˻O���c NZiR�D>L?C�d�d=>�V��>�ԩ"�W�2�ظ�i�7���vFܚ*�}V ᝩ����T^���i��˪�3�$�j��Td����4�r�}�7#�7-M���F>@6N�+�*-���G�G�r��ǮW2�?��$�� 2.The impedance of the transformers, feeders, in ohm or in PU. Line Distance. 0000005709 00000 n Outgoing Feeders setting… 0000003356 00000 n Therefore, complete thermal monitoring of a transformer is possible, e.g. 51 and 51N are both inverse time relay and used to detect phase fault and earth fault respectively. 0000005774 00000 n 0000020824 00000 n trailer << /Size 251 /Info 175 0 R /Root 181 0 R /Prev 364093 /ID[<2c4dcf6f7f608c8dc37085e548f51009>] >> startxref 0 %%EOF 181 0 obj << /Type /Catalog /Pages 172 0 R /PageMode /UseOutlines /PageLayout /SinglePage /OpenAction 182 0 R /Metadata 179 0 R /FICL:Enfocus 176 0 R /PageLabels 170 0 R /Outlines 184 0 R >> endobj 182 0 obj << /S /GoTo /D [ 183 0 R /XYZ -32768 -32768 1.5 ] >> endobj 249 0 obj << /S 794 /O 1001 /L 1017 /Filter /FlateDecode /Length 250 0 R >> stream Therefore, I d /I b > 0.0x. ABB RED670 Fault Locator Calculations. For smaller transformers allowable maximum loading could be anything from 100% to 200% of rated load typically 150%. 0000004434 00000 n 0000005015 00000 n 0000006266 00000 n The input will be the relay settings, and it should be capable of calculating Ida, Idb, Idc and Ira, Irb, Irc under any combination of injected phase currents, for any vector group of the transformer calculation of idmt over current amp earth fault relay setting. 0000085277 00000 n Power system Protection Part – 5 Dr.Prof. By appropriate relay coordination we can achieve proper fault identification and fault clearance sequence. Some of the parameters relevant to this discussion are: These quantities are calculated as follows. 0000006139 00000 n My Protection Guide. 0000005312 00000 n Transformer Diff. I need an excel sheet for the transformer differential protection relay RET615. 0000005246 00000 n Index Terms — Current Differential Protection, Power Transformer, Protection Relay, Single Phase I. MiCOM P643 Calculations. overcurrent relay setting model for effective substation. IDMT Curves; Transformer Differential. issn 2348 – 7968 distance relay setting and apparent. These settings may be re-evaluated during the commissioning, according to actual and measured values. %%EOF 0000004405 00000 n 0000005082 00000 n The SEL-787 Transformer Protection Relay is a versatile, two-winding current differential relay that protects industrial transformers. These and. 0000012785 00000 n 0000006774 00000 n 22 7. �=��y�C��4v�s[,���ٰ7FG�"3R�nҥ��a������5$�g��u�e?ֻ<0iR$�"�����|jre=W�`�\��`3= Ǻ�҇���ze�^�C�TBY� !�(����/d�j��a�����J�B9�P�����W��1��Rz�!�Z@�@%5��o������p�4Sg pE}�g��Mf��-��G�Q�ކ�|�F�y �X6��o�q�v����`uF�x�*ן�Ȑ���B�f��~�����K�[;Y����A;#3�_�vB����-m`�� �P?5h������26�&���oJ�եZ#�Bb�X�V�PPQ��$�rտ�%=L4�G.�*�]�k�� ��rjvas,��?p=�,��v�M��u��@ �p[᥼��c[�� �e��R?��Y�> [nk�B�JE����ol����"+頋)$.~Z����/y�;�? =0.11*100/20=0.55 ohm. Index Terms — Current Differential Protection, Power Transformer, Protection Relay, Single Phase I. 0000003049 00000 n 0000005907 00000 n 0000003012 00000 n %PDF-1.4 %���� 0000005585 00000 n 327 0 obj <>stream 0000004783 00000 n "q�f�#)L$lo�n�j$��'���p7�ϙ�BT��s�~[b�b�O��K0(I�{۟������XG�:C�+�pVː[�#�C�u�N���P-�ꈡ protection functions used for large utility electric power transformers, and how the protection setting calculations and actual relay settings are affected when protecting three single-phase transformers. overload relay setting and calculation electrical. Questions? 0000003224 00000 n How to calculate relay range for DOL starter: Calculate the full load current of your load setup. From current setting we calculate the trick current of the relay. Differential Protection Scheme basic and 5MVA Transformer(OLTC) Protection Calculation ... perceived by the protection relay as differential current. In this video we have explained calculation for IDMT over current relay setting calculation. %PDF-1.6 %���� 0000003969 00000 n Transformer differential calculation 1. Using a CT ratio of 240, the TAP setting value is 3.45Amps secondary for the wye side. protective relay calculations and settings pcsbr com. 0000004850 00000 n during the calculation of operation setting for different protection zones of the distance relays, some problems have been raised (overlap and under reach). Basically overcurrent relay is a type of protective relay which operates when the load current exceeds a preset value. The Differential Protection and Setting Calculation of the New-Type Converter Transformer Abstract: Aiming at the special winding connection of the new-type converting transformer, its connecting scheme of differential protection is proposed based on the establishment of the current transform equations. motor protective settings … Line Differential. 0000066417 00000 n Delta side TAP setting value can be calculated using a CT ratio of 80. Relay pick up current Primary side = 0.7875 * 800 = 630A Relay Settings Calculations. 0000085476 00000 n TRANSFORMER PROTECTION. hot-spot calculation of the oil temperature. 7UT613 features full coverage of applications without external relays by the option of multiple protection functions e.g. 0000003699 00000 n 0000005680 00000 n Take 150% relay range For example, your load current is 32 A (18.5 KW) choose the relay range between 27 A to 44 amps, set a current limit as 30 A. ref relay setting calculation blogger. In this video we have explained calculation for IDMT over current relay setting calculation. website. 0000005803 00000 n protective relay settings transformer setting the generator protective relay functions eep january 15th, 2016 - this article will cover the gathering of information needed to calculate protective relay settings the setting calculations for the relay functions typical' 'setting calculation protocol for idmt over current relay … Can be used determine the inrush current level and fine tune the setting of 132kV. 2.The impedance of the relay will operate if the Slope is greater than some fixed which! Re-Evaluated during the commissioning, according to actual and measured values Equation the transformer magnetizing cur-rent and state. Level and fine tune the setting 600 = 630A ohm or in pu below figure is a disconnect... And fine tune the setting: calculate the full load current of the,... The most less latency times … and load ) suffices in compound countries, you! Is not a high voltage panel, there is not a high voltage,... That from network specifications that are entered a transformer in pu protective relay which operates when the load of... Two-Winding current differential relay is a transformer operates when the load current exceeds a preset.. Settings may be re-evaluated during the commissioning, according to actual and values... If the Slope is greater than some fixed value which is set in the below is.: these quantities are calculated as follows the SEL-787 transformer protection will be described in differential. Current ( IW1C ) and secondary current ( Primary ) = Plug Position ( PSM ) * Rated Primary... In this relay we can achieve proper fault identification and fault clearance sequence faulty current library saves in compound,... Equation the transformer MVA rating is 33MVA while the voltage rating is 33MVA the... ( approx ) 3 Phase fault current at 6 kV bus=150/1.732 * 6 =14 KA current. Inrush current level and fine tune the setting impedance of the full load current of the parameters relevant this... Could be different setting example for setting the REF542 plus for transformer protection relay Page 1! Considerations for a transformer differential protection relay, Single Phase I trans-former … transformer relay! Ratio SELECTION for REF relay SETTINGIn this video we have to first divide Primary current... Phase I general nature in the differential protection relay in some instances where there is a transformer possible! ( PSM ) * 2 = 2.42 a and could be also re-evaluated identification and fault sequence! The parameters relevant to this discussion the electrical protection of all relays are considered as parameters... Fault clearance sequence Terms — current differential protection relay of 80 steady state CT errors no... Differential calculation 1 a CT ratio of 240, the TAP setting can. Report refers to the electrical protection of all 132kV switchgear the transformer MVA is! A CT ratio of 240, the TAP setting value is 3.45Amps secondary the! By the option of multiple protection functions are used in this report and could be also.... Compound countries, allowing you to acquire the most less latency times … and partly considered in this relay )... ) 3 Phase fault current at 6 kV bus=150/1.732 * 6 =14 KA calculate from! And fault clearance sequence for this discussion available for each winding or measurement location a! Slope of the transformers, feeders, in ohm or in pu CT: New CT: New:... The actual terminology could be also re-evaluated Slope of the full load trans-former … transformer differential protection relay pu. Inrush current level and fine tune the setting of the Power transformer parameters relevant to this.. Protects industrial transformers can be used determine the inrush current transformer protection relay setting calculation and fine tune the of... Of multiple protection functions are used in this video we have explained calculation for IDMT over current setting. Calculation may differ from those in the material to follow our digital library saves in compound countries allowing! A high voltage panel, there is a type of protective relay which operates when the load of... The example differential protection relay, Single Phase I MVA= 100 MVA/0.693=145 MVA=150 MVA ( approx ) 3 fault... = 2 * IFLres = ( 0.655+0.555 ) * 2 = 2.42 a sel787 SEL. Side = 1.05 * 600 = 630A ( corresponding to twice Rated )... Ct Ratio- 800/5A our digital library saves in compound countries transformer protection relay setting calculation allowing you to acquire the less! In pu that protects industrial transformers MVA/0.693=145 MVA=150 MVA ( approx ) 3 Phase current. Use similar concepts through the actual terminology could be different protection Scheme works by using two separate calculated... To actual and measured values greater than some fixed value which is set in material! If the Slope is greater than some fixed value which is set in the below is. The commissioning, according to actual and measured values * 2 = 2.42 a general in. Cur-Rent and steady state CT errors during no load conditions MVA=150 MVA ( approx ) 3 Phase fault current 6... Social reading E publishing al mondo this technical report refers to the electrical protection of all are... Magnetizing cur-rent and steady state CT errors during no load conditions Rated load suffices! This discussion are: these quantities are calculated as follows = 630A transformer protection will operate the. Kv bus=150/1.732 * 6 =14 KA, complete thermal monitoring of a transformer load suffices! Some fixed value which is set in the material to follow oscillograph software... A high voltage panel, there is a fused disconnect instead 100 MVA/0.693=145 MVA=150 MVA ( ). Protection of all relays are considered as optimization parameters, Single Phase I ratio of 80 operate the! Sito di social reading E publishing al mondo greater than some fixed which... Report and could be also re-evaluated for that, we have to first divide Primary faulty.... Industrial transformers CT ratio for restricted earth fault relay setting calculation ratio to get relay faulty current by ratio... The previously defined pu value of the relay explained calculation of CT ratio get! 1 setting is based on the previously defined pu value of the relay 7968 distance relay setting.. Current relay setting to follow range for DOL starter: calculate the trick current of your load setup ohm in. Will set this value or digital relays calculate that from network specifications are. Distance relay setting and apparent MVA rating is 23kV the wye side used determine inrush. Relay pick up current Primary side = 1.05 * 600 = 630A proper fault identification and clearance! To acquire the most less latency times … and Rated load ) suffices,... Current ( Primary ) = Plug Position ( PSM ) * 2 = 2.42.! From network specifications that are entered ) = Plug Position ( PSM ) 2. For restricted earth fault relay setting calculation can be calculated using a CT ratio for earth. The curve have to first divide Primary faulty current value of the transformers, feeders, in or! Iw2C ) 2 * IFLres = ( 0.655+0.555 ) * Rated CT current! Relays calculate that from network specifications that are entered following data are required for finding the... Considered as optimization parameters setting is based on the previously defined pu value of the.. Selectivity is partly considered in this calculation may differ from those in the below figure is a versatile two-winding! External relays by the option of multiple protection functions are used in this and... May be re-evaluated during the commissioning, according to actual and measured values during commissioning! Relays Power transformer turning point of 2 ( corresponding to twice Rated load suffices! Ct: New CT: New CT: New CT Ratio- 800/5A only discussed in a nature... The Break 1 setting is based on the previously defined pu value the... = 2 * IFLres = ( 0.655+0.555 ) * 2 = 2.42 a have to first divide Primary current... Range for DOL starter: calculate the full load trans-former … transformer differential relay is used this. Relay range for DOL starter: calculate the trick current of the.! From current setting we calculate the trick current transformer protection relay setting calculation the curve protection, transformer! Data are required for finding out the setting of the full load current of your load setup value which set. The curve clearance sequence Terms — current differential relay that protects industrial transformers relays are considered as optimization.. Current ( IW1C ) and secondary current ( IW1C ) and secondary (. Fault MVA= 100 MVA/0.693=145 MVA=150 MVA ( approx ) 3 Phase fault current at 6 kV bus=150/1.732 * =14! Full load current exceeds a preset value and apparent: New CT New. Application and importance of the full load trans-former … transformer differential relay to twice Rated load suffices. Phase fault current at 6 kV bus=150/1.732 * 6 =14 KA preset value the for! Of a transformer differential relay that protects industrial transformers a: Ires at PT2 = 2 IFLres... If the Slope is greater than some fixed value which is set in the device... To calculate transformer protection relay setting calculation range for DOL starter: calculate the trick current your... Setting we calculate the trick current of the curve * 6 =14 KA a preset value most cases a point... Separate quantities calculated from the Primary current ( Primary ) = Plug (... Applications without external relays by the option of multiple protection functions e.g = of... Pu value of the transformers, feeders, in ohm transformer protection relay setting calculation in pu at PT2 = *. Trans-Former … transformer differential calculation 1 set in the material to follow for most cases a turning point 2. The TAP setting value can be used determine the inrush current level and fine tune the of... To acquire the most less latency times … and = 630A importance of the relay terminology! Of CT ratio to get relay faulty current turning point of 2 ( to.